The 4209U Group Zoning Module streamlines large or expanded
system installation. In retrofit applications, installers can utilize existing
hardwired smoke detectors (UL Compatibility Listed) and wiring to expand
system-wide smoke detector capability and capacity. The 4209U also offers
flexible zone configurations to meet the varying demands of commercial
applications.
Features
Combines two-wire smoke detectors from an area of the
protected premises into group zones
Can be attached remotely or at the panel
All loops are EOLR supervised (2K, supplied)
Provides power and supervision for two-wire industry
standard smoke detectors (review UL compatibility listing)
Each loop can support up to 16 smoke detectors in the
non-grouped mode, or in the grouped mode
Supports four-wire smoke detectors
Uses two or four V-Plex addresses
Supports either dip switch or serial number
applications
UL864 Listed NFPA 72 compliant
Separate DC input, no current drain from primary
V-Plex loop
Can greatly expand smoke detection coverage cost
effectively